Zhiyue Group Co., Ltd.
Products
Contact Us
  • Contact Person : Ms. Ni Nico
  • Company Name : Zhiyue Group Co., Ltd.
  • Tel : 86-577-62786608
  • Fax : 86-577-62786608
  • Address : Zhejiang,Yueqing,Shangfeng Industrial Area,Liushi Town
  • Country/Region : China
  • Zip : 325604

harmonic filter reactor

harmonic filter reactor
Product Detailed
Related Categories:Inductors
1.restrain the harmonic blow up effectively2. improve the voltage wave form3.restraint switch on inrush current and so on

DESCRIPTION:

 

This series low voltage series connected reactor is used in low voltage reactive compensation device, and series connected with capacitor, when the low voltage power net have a great quantity of harmonic source such as rectifying and defector, which produce high harmonic will seriously damage the main transformer, and other electrical device. The reactor series connected with capacitor will restrain the harmonic blow up effectively, improve the voltage wave form and system’s power factor, and restraint switch on inrush current and operation over voltage, protect the capacitor effectively.

TECHNICAL DATA:

Can use in 400V and 660V system.Reactance ratio: 1%, 6%, 7%, 12%, 13%, 14% and so on.Rated insulation level: 3KV/min.The temperature rise limited value of the reactor each part: the iron core can not exceed 85K, and the coil can not exceed 95K.The reactor noise can not exceed 50dB.The reactor can work for long time when the work frequency and harmonic current not exceed 1.35 times rated current.Linearity degree of reactance value: the value of ratio between reactance value in 1.8 times rated current and reactance value in rated current can not lower than 0.95.For three phase reactor, the imbalance of each two phase reactance value can not exceed 3%.Service temperature range, H degree, higher than 180 degrees Celsius.

SPECIFICATION:

The specification for 6% reactance ratio:

Model

Capacitor Output

(kvar)

Reactor output

(kvar)

Inductance

(mH)

Rated current

(A)

CKSG-0.3/0.4-6%

5

0.3

3X7.74

6.4

CKSG-0.45/0.4-6%

7.5

0.45

3X5.16

9.6

CKSG-0.6/0.4-6%

10

0.6

3X3.87

12.8

CKSG-0.72/0.4-6%

12

0.72

3X3.22

15.4

CKSG-0.84/0.4-6%

14

0.84

3X2.76

18.0

CKSG-0.9/0.4-6%

15

0.9

3X2.58

19.2

CKSG-0.96/0.4-6%

16

0.96

3X2.42

20.5

CKSG-1.2/0.4-6%

20

1.2

3X1.93

25.7

CKSG-1.44/0.4-6%

24

1.44

3X1.61

30.8

CKSG-1.5/0.4-6%

25

1.5

3X1.55

32.1

CKSG-1.8/0.4-6%

30

1.8

3X1.29

38.5

CKSG-2.1/0.4-6%

35

2.1

3X1.11

44.9

CKSG-2.4/0.4-6%

40

2.4

3X0.97

51.3

CKSG-2.7/0.4-6%

45

2.7

3X0.86

57.7

CKSG-3/0.4-6%

50

3

3X0.77

64.2

CKSG-3.6/0.4-6%

60

3.6

3X0.64

77.0

CKSG-4.8/0.4-6%

80

4.8

3X0.48

102.6

Note: CKSG Type, 400V system, three phase, 6% reactance ratio, the capacitor voltage 450V

The specification for 12% reactance ratio:

Model

Capacitor Output

(kvar)

Reactor output

(kvar)

Inductance

(mH)

Rated current

(A)

CKSG-0.6/0.4-12%

5

0.6

3X17.61

6.0

CKSG-0.9/0.4-12%

7.5

0.9

3X11.74

9.0

CKSG-1.2/0.4-12%

10

1.2

3X8.81

12.0

CKSG-1.44/0.4-12%

12

1.44

3X7.34

14.4

CKSG-1.68/0.4-12%

14

1.68

3X6.29

16.8

CKSG-1.8/0.4-12%

15

1.8

3X5.87

18.0

CKSG-1.92/0.4-12%

16

1.92

3X5.50

19.2

CKSG-2.4/0.4-12%

20

2.4

3X4.40

24.1

CKSG-2.88/0.4-12%

24

2.88

3X3.67

28.9

CKSG-3/0.4-12%

25

3

3X3.52

30.1

CKSG-3.6/0.4-12%

30

3.6

3X2.94

36.1

CKSG-4.2/0.4-12%

35

4.2

3X2.52

42.1

CKSG-4.8/0.4-12%

40

4.8

3X2.20

48.1

CKSG-5.4/0.4-12%

45

5.4

3X1.96

54.1

CKSG-6/0.4-12%

50

6

3X1.76

60.1

CKSG-7.2/0.4-12%

60

7.2

3X1.47

72.2

CKSG-9.6/0.4-12%

80

9.6

3X1.10

96.2

Note: CKSG Type, 400V system, three phase, 12% reactance ratio, the capacitor voltage 450V

harmonic filter reactor